Permit: T08CM03163

Parcel: 10712225A


Addresses:

2835 N STONE AV #04


Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T08CM03163

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
06/03/2010 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
05/25/2010 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEE NOTE #1 BOND JUMPER PER 250-66
05/21/2010 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) BONDING REQUIRED AHEAD OF SERVICE DISC. PER 250.92 NEC
2) ISLOATE NEUTRALS AND GROUNDS
3) BOND BUSHING REQUIRED FOR METAL RACEWAY FOR GEC