Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM03152
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/08/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/07/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. OPEN WIRING BY PANEL IN BACK ROOM 2. LV CABLING TO BE SUPPORTED OFF T-BAR SEE NOTES INSP. 12/15/08 |
|
12/15/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* NEXT INSPECTION AFTER CASH WRAP MOVE *NOTE: 725.24, 800.24, 300.11 WILL APPLY FOR VDV CABLING ABOVE CEILING 1. FINISH LABELING CI. 12 & 19 & 23 & 25 & 28 -- NO ABBREVIATIONS |
|
12/12/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FINISH PANEL, SENSORS AND CASH WRAP OK TEMPORARY |
|
12/08/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PANEL DIRECTORY TO BE AS PER 408.4 2. FINISH CASH WRAP IF AFTER HOURS INSPECTION IS NEEDED CALL JASON JAWORSKY @ 909-5147 TO SCHEDULE. A CHARGE OF $150.00 WILL BE NEEDED IN A CHECK OR MONEY ORDER THE DAY OF THE INSPECTION |