Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/06/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/16/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. GROUND JUNCTION BOX & CONTACTOR BOX -- 250.148 2. FULLY IDENTIFY UNGROUNDED CONDUCTOR -- 200.7 3. CONDUCTOR TO BE LISTED -- 110.3 (B) 4. ONLY ONE CONDUCTOR UNDER TERMINAL SCREW 5. FILL UNUSED OPENING IN JUNCTION BOX |