Permit: T08CM03114

Parcel: 141310750

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T08CM03114

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
11/10/2008 FRAMING Approved IVRS - Inspection :*
1) NOTE: BOND METAL BOX AT RANGE, WILL CHECK AT FINAL
10/31/2008 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TWO H.D.'S HTT16 AT FRONT BEDROOM ADDED AFTER OSB INSPECTION, NOT NAILED TO EXT. SHEATHING, REDUCING SIZE OF SHEARWALL
2) UF WIRE AT KITCHEN ISLAND NOT PROTECTED AT SLAB TO PLATE-TO BE IN CONDUIT
3) FOR NEXT HOUSE PLEASE HAVE FOUNDATION PLAN, DETAILS FOR COLS. FOR THIS TYPE OF PORCH
10/30/2008 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO PLANS OR PERMIT ON SITE