Permit: T08CM03084

Parcel: 130056720


Addresses:

2425 S EDMONDSON AV


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM03084

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/26/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
1) EXHAUST FAN NOT WIRED
2) CONDENSATE LINE NOT FINISHED
3) #8 ROMEX CU. FEED AT 60 DEGREE IS GOOD FOR MAX 40 AMPS ROOF UNIT, VERIFY WITH MECH CONTRACTOR
4) 3/4" DIAMETER H20 SUPPLY TAKEN FROM WHAT SIZE PIPE ?
PLAN CALLS FOR 1" MINIMUM MAIN LINE TAP FOR 3/4
12/23/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING 110 SERVICE GFCI ROOF TOP
2) MISSING SMOKE DETECTOR PER PLAN-STORAGE NORTH ENTRANCE MASTER