Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM03084
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/26/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* 1) EXHAUST FAN NOT WIRED 2) CONDENSATE LINE NOT FINISHED 3) #8 ROMEX CU. FEED AT 60 DEGREE IS GOOD FOR MAX 40 AMPS ROOF UNIT, VERIFY WITH MECH CONTRACTOR 4) 3/4" DIAMETER H20 SUPPLY TAKEN FROM WHAT SIZE PIPE ? PLAN CALLS FOR 1" MINIMUM MAIN LINE TAP FOR 3/4 |
|
12/23/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING 110 SERVICE GFCI ROOF TOP 2) MISSING SMOKE DETECTOR PER PLAN-STORAGE NORTH ENTRANCE MASTER |