Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/08/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/19/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* USE APPROVED METHODS TO SECURE NM CABLE OK AFTER CORRECTIONS |
|
| 11/18/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* *A REFEE MAY BE ASSESED IF WORK IS NOT PROGRESSING 1. FILL UNUSED OPENING IN OLD HANDY BOX 2. USE APPROVED STRAPS FOR NM CABLE NOT M/C 3. VERIFY BOX FILL AT NEW TIE-IN LOCATION |
|
| 11/10/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. GROUND METAL BOXES 2. SECURE NM CABLES WITHIN 12" OF BOXES 3. WHERE DOES POWER (HOMERUN) COME FROM? IF FROM HANDY BOX VERIFY FILL CAPACITY |
|
| 11/03/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 10/24/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS ROOM SW BEDROOM |
|
| 10/23/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SWITCH BOX OVERFILLED 2. GROUND METAL JUNCTION BOX |