Permit: T08CM03079

Parcel: 110082070

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/17/2008 ELECTRIC - FINAL Approved OK PANEL AND FAULTS
11/13/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. NO PLANS ON SITE
2. COMPLETE PREVIOUS INSPECTION ITEMS
11/07/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO REVISE PLANS FOR SCOPE OF WORK INCLUDING REPLACEMENT OF 2 PANELS
2. PANELS DO NOT HAVE PROPER WORKING CLEARANCES
ONE PANEL IS LOCATED IN LINEN CLOSET NEAR COMBUSTIBLE MATERIAL AND IS IN VIOLATION OF NEC 240 & 110
3. NEED TO HAVE ELECTRICAL CONTRACTOR ON SITE FOR ALL FUTURE INSPECTIONS