Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/10/2008 | FRAMING | Approved | IVRS - Inspection :* | |
| 11/07/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MISSING AB GARAGE PLATE JOINT WEST WALL 2. MISSING CRIPPLE STUDS @ HEADERS INTERIOR THROUGHOUT 3. SECURE 4-GANG BOX KITCHEN 4. DAMAGED FIRE BLOCK KITCHEN CABINET WALL 5. MISSING FIRE BLOCK MASTER 45 WALL 6. MISSING FIRE BLOCK MASTER WATER CLOSET ROOM 7. LOOSE BOTTOM PLATE BEDROOM 3 CLOSET 8. BLOCK WH PLENUM |