Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/14/2008 | ELECTRIC - FINAL | Approved | 1) OK TO CLEAR ECO 2) STATE OFFICE OF MANUFACTURE RESPONSIBLE FOR FEEDER FROM 100 A DISCONNECTS O/S MAIN BLDG |
|
| 10/10/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. BOND BLD. STEEL TO NEW SERVICE GROUND ELECTRODE SYSTEM, PHASE TAPE FEEDERS TO ID VOLTAGE BOND JUMPERS ON SUPPLY SIDE OF SERVICE TO BE SIZED BY 250.66 NEC 2. BOND GROUNDING SYSTEM TO ENCLOSURE OF DISCONNECT AT SERVICE |
|
| 10/01/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOND RISER INTO METER 2. BOND NIPPLE BETWEEN METER & DISCONNECT 3. INSTALL MAIN BONDING SERVICE DISCONNECT 4. "MARK SERVICE DISCONNECT" 5. REMOVE NEUTRAL FROM 480V SOURCE 6. CONNECT GROUNDING ELECTRODE CONDUCTOR TO BUILDING STEEL 7. ONE WIRE PER TERMINAL 8. INSTALLATION NOT PER PLAN. CANNOT SEE ELECTRIC PLAN EXAMINER REVIEW. HAVE ENGINEER REVIEW INSTALLATION INSTALL PER PLANS AND NEC 9. SPLIT BOLT CONNECTORS NOT LISTED FOR MORE THAN 2 WIRE TERMINATIONS 10. HAVE MORE THAN ONE SERVICE TO BUILDING OR HAVE SERVICE DISCONNECTS NOT GROUPED 11. HAVE MORE THAN 1 FEEDER TO TRAILER CODE ALLOWS ONLY ONE |