Permit: T08CM03052

Parcel: 10603148A


Addresses:

125 W YAVAPAI RD


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T08CM03052

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/30/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
03/26/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
03/24/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. VERIFY R-VALUE INTERIOR DUCT
2. DUCT ON ROOF DOES NOT HAVE AN R-VALUE OF 8
PROVIDE 2" MIN. DUCT LINER
3. RTU's ARE OVERFUSED
4. PROVIDE AIR BALANCE REPORT
03/19/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/05/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*