Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T08CM03052
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2009 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 03/26/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/24/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. VERIFY R-VALUE INTERIOR DUCT 2. DUCT ON ROOF DOES NOT HAVE AN R-VALUE OF 8 PROVIDE 2" MIN. DUCT LINER 3. RTU's ARE OVERFUSED 4. PROVIDE AIR BALANCE REPORT |
|
| 03/19/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/05/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |