Permit: T08CM03046

Parcel: 116022810

Inspection Status: Not ready for Inspection

Inspection History: FRAMING

Permit Number - T08CM03046

Inspection Description - FRAMING

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
04/28/2010 FRAMING Not ready for Inspection IVRS - Inspection :*
11/23/2009 FRAMING Not ready for Inspection IVRS - Inspection :*
1) NOT READY, NO ANSWER AT DOOR
06/24/2009 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MAKE INSPECTED AREA ACCESSIBLE
2) SECURE ALL ROMEX 8" FROM BOXES
3) TREAT ALL PLATES TOUCHING SLAB
4) ? WEEP STUCCO ON SLAB
5) STOPPED INSPECTION
04/27/2009 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ACCESS TO HOME 10:13 AM
2) IF APPOINTMENT IS NEEDED LEAVE MSG ON VOICE MAIL
12/18/2008 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SOLE PLATE ANCHOR BOLTS NEED TO BE 1/2" X 6"
2) NEED PROTECTION PLATES ON WIRING THRU STUDS-WHERE LESS THAN 1 1/4
3) ALL ELECTRICAL BARS MUST BE IN PLACE
4) ELECTRIC WIRING NEEDS TO BE COMPLETED
5) EXPOSE STUCCO MESH TO INSPECT ON MOISTURE BARRIER IN ONE LOCATION, OWNER MAY CHOOSE HIS SPOT