Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T08CM03032
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/20/2008 | FRAMING | Approved | IVRS - Inspection :* | |
11/17/2008 | FRAMING | Denied | 1) NEED TO FIRE SEAL CHASE (PLUMBING) AT GARAGE CORNER 2) NEED PROTECTION PLATE ON CIRCUIT WIRES AT ENTRY NOOK 3) NEED PROTECTION PLATE ON 1 1/2 ABS VENT AT ENTRY NOOK 2ND FLOOR AND SOLE PLATE 4) BLK MECHANICAL DUCT VENT 3 SIDES-POWDER ROOM 5) CHASE 2ND FLOOR AT MASTER BATH NEEDS TO BE FIRESEALED 6) VERIFY DEPTH AND TYPE OF BOLT USED FOR HTT22 AT INTERIOR SHEARWALL 7) STUCCO NOT COMPLETED AT ARCHED WINDOW-SOUTH BEDROOM 8) WASHER DRAIN LINE NOT PER PLAN |