Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T08CM03030

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM03030

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/12/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/11/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. LABEL PANEL AS PER 408.4 -- NO ABBREVIATIONS, DISTINGUISHABLE FROM ONE ANOTHER & CORRECT
2. CANNOT USE HANDLE TIE FOR INDIVIDUAL CIRCUITS
3. BOXES IN COMBUSTIBLE TO BE FLUSH

*RECEIVED LETTER FOR TRANSFORMER