Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T08CM03030

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/12/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
12/09/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO TILE
1. WAITING ON LETTER
12/05/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. BOXES OVERFILLED
2. SUPPORT VDV CABLING 725.24, 800.24, 300.11
3. CANNOT STACK LUGS AT XO TERMINAL
4. PLANS CALL FOR NEW TRANSFORMER -- THIS IS USED
5. CLEAN SURFACE UNDER LUG ON RED IRON
6. REMOVE TEMP LIGHTS