Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/17/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEAL OPEN KNOCKOUTS PANELS 2. NEED PROPER WORKING CLEARANCES IN FRONT OF PANELS 3. HAVE 1/2" EMT ON ROOF NOT GROUNDED 4. PLEASE VERIFY PERMITS FOR NEW ELECTRIC WORK IN SHOP. ADDING PANELS ETC. 5. GROUNDS & NEUTRALS TO BE SEPARATE IN SUB-PANEL 6. MARK DC DISCONNECT PER PLANS |
|
| 09/15/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* BLDG's LOCKED NO ONE ON SITE |