Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/16/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 10/20/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. CHECKED WELDS ON GREASE DUCT 2. REPAIR 1 LEAK 3. OK 1ST LAYER OF FIRE WRAP 4. WRAP MUST EXTEND TO TOP OF DUCT 5. EXTEND 20 X 20 DUCT TO TOP OF CURB AS PER PLAN 6. PROVIDE PERMITS FOR 2 NEW AC UNITS ON ROOF 7. PROVIDE DUCT SMOKE DETECTORS FOR BOTH UNITS. |