Permit: T08CM02987

Parcel: 13329015K


Addresses:

8585 E BROADWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/15/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
11/28/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. COMPLETE ALL WORK INCLUDING INSTALLATION OF ALL BEVERAGE EQUIPMENT
2. EACH PIECE OF EQUIPMENT THAT MAY CAUSE POLLUTION OR CONTAMINATION OF THE WATER SYSTEM REQUIRES BACKFLOW PROTECTION.
3. SEE UPC 603.2 FOR DEVICES OR METHODS
4. PROVIDE BACKFLOW TEST REPORTS
5. PROVIDE HOSE BIB VACUUM BREAKERS
6. PROVIDE WATER STERILIZATION AND DOCUMENTATION
PER 609.9
7. INSTALL PLUGS IN ANY OPEN CLEANOUTS
8. SEAL W/APPROVED THREAD SEALANT
9. COMPLY W/THE CODE REQUIREMENTS FOR INDIRECT WASTE PIPING AND RECEPTORS
10. 1" MIN. AIR GAP REQUIRED 801.1
11. I.W PIPES MAY NOT REDUCE IN SIZE 801.2.1
12. I.W PIPES EXCEEDING 5' SHALL BE DIRECTLY TRAPPED 803
13. CLEANOUTS REQUIRED AT CHANGES OF DIRECTION
14. PIPING AND RECEPTORS SHALL BE OF SUCH CAPACITY TO PREVENT FLOODING - 804.1
15. PROVIDE 1/4" PER FOOT SLOPE
16. HAND SINK TAIL PIECE AND CAULK
17. WC OPEN FRONT SEATS
18. AS A COURTESY, A GAS CARD HAS BEEN PROVIDED
11/25/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
COMPLY W/BASIC PLUMBING CODES
COMPLETE ALL WORK, FOLLOW PLAN SPECS
OWNER AGGRESSIVE
INSPECTION STOPPED