Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/24/2008 | FRAMING | Approved | IVRS - Inspection :* | |
| 11/04/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED BANG PLATE AT TOP PLATE FOR GANG BOX INTO GARAGE HALLWAY DOOR WIRING 2) NEED PROTECTION PLATES IN ELECTRIC WIRING THROUGHOUT HOUSE 3) CONDUCTORS TO SMOKIES MUST BE COMPLETED (IN BOXES) 4) NEED COPY OF 3RD PARTY INSPECTION FOR RETRO ON BRACED WALL BEDROOM #3 LIVING ROOM 5) NEED STUD SHOES ON OVER BOARD STUDS FOR KITCHEN SINK VENT 6) MASTER BATH GFI FOR DBL LAVS IN WRONG LOCATION NEED TO INSTALL AT WALL IN BETWEEN SINKS OR ADD 1 AT EACH END 7) ITEM #7 FROM PRIOR INSPECTION NOT CORRECTED |
|
| 10/31/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STAPLE INFO PEX FEEDING WATER SOFTNER ? 2) GROUND GARAGE PANCAKE BOXES 3) REMOVE MESH STAPLES BEHIND HOMERUNS 4) NAIL OFF PEX OVERBORE FHA STRAPS IN GARAGE 5) SHIM GIRDER TRUSS STUDS IN GARGAGE AND BEDROOM 6) BANG PLATE CONDENSATE DRAIN WHERE NEEDED 7) RIDGE VENT NOT PRESENT PER PLAN 8) BANG PLATE #14 WIRE AT EAST GARAGE TOP PLATE 9) NO WATER IN DWV 10) STOPPED INSPECTION AFTER GARAGE ONLY |