Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T08CM02953
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/23/2009 | FIRE - FINAL | Approved | ||
03/20/2009 | FIRE - FINAL | Partial Approval | OK for Temp. CofO with bond posted. 3/20/09. Return air for hood system is connected to the system. It must shut -off upon activation of system. Air was not shutting -off. Bad relay. All other parts of hood systems were tested and approved. It was determined that due to the fact that all appliances were protected, it being a new system with negative grease build-up and the building being fully sprinklered, it was safe to operate with a temp. Cof O. Electrician on site awaiting a new relay to be delivered. Approved by Dave Mann. |