Permit: T08CM02938

Parcel: 11016223A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T08CM02938

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/29/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
05/18/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. PLEASE PROVIDE REVISED PLANS FOR THE ELIMINATION OF THE MINI-SPLIT SYSTEM AND ADDITION OF THE EXHAUST FAN
2. EXHAUST FAN WILL REQUIRE MAKE UP AIR
3. MARK UNIT DATA PLATES WITH PROPER HEAT STRIP AND FUSE ACCORDINGLY
4. PROVIDE SCREENS IN T-TOPS ON ROOF EXCEPT FOR
DRYER VENT
5. PERMANENTLY I.D. UNITS AND DISCONNECTS
6. BATHROOM EXHAUST FANS TO BE ON A TIME CLOCK
AS PER PLANS
7. DUCT SMOKE DETECTOR TEST OK
8. AIR BALANCE OK
04/22/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1. OK FOR CEILING TILES
2. PROVIDE PROPER REDUCER AT EXHAUST FANS
WILL CHECK ON FINAL
3. REVISE PLANS IF DELETING OR ADDING ANY EQUIPMENT
03/09/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*