Permit: T08CM02922

Parcel: 13604328C

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T08CM02922

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/12/2008 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
11/10/2008 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO DETAILED LIST ON SITE
SEE DETAIL 4 M1
11/07/2008 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLANS REQUIRE INSULATED COPPER DRAIN LINES FOR CONDENSATE.
2. PROVIDE A LETTER FROM ENGINEER IF USING PVC.
3. WILL CHECK ON FINAL
4. FLEX DUCTS NOT INSTALLED PER DETAIL ON PLANS
5. PROVIDE FILTERS IN A/C UNITS
6. REPAIR INSULATION IN 1 A/C UNIT
11/04/2008 MECHANICAL - ABOVE CEILING Cancelled CANCELLED PER CONTRACTOR WILLIAM RIVAS #331-5701
11/04/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
09/26/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. PROVIDE EXHAUST DUCT TO NEW FAN
2. RELOCATE CONDENSATE DRAIN TO MOP SINK
3. PROVIDE COPPER, INSULATED, CONDENSATE PIPING
4. PROVIDE BACKING AROUND CEILING BOXES
5. DO NOT SUPPORT ANYTHING WITH NYLON BANDS
6. INSTALL FLEX DUCTS AS PER DETAIL ON PLANS