Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T08CM02922
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/12/2008 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
11/10/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO DETAILED LIST ON SITE SEE DETAIL 4 M1 |
|
11/07/2008 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLANS REQUIRE INSULATED COPPER DRAIN LINES FOR CONDENSATE. 2. PROVIDE A LETTER FROM ENGINEER IF USING PVC. 3. WILL CHECK ON FINAL 4. FLEX DUCTS NOT INSTALLED PER DETAIL ON PLANS 5. PROVIDE FILTERS IN A/C UNITS 6. REPAIR INSULATION IN 1 A/C UNIT |
|
11/04/2008 | MECHANICAL - ABOVE CEILING | Cancelled | CANCELLED PER CONTRACTOR WILLIAM RIVAS #331-5701 | |
11/04/2008 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
09/26/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. PROVIDE EXHAUST DUCT TO NEW FAN 2. RELOCATE CONDENSATE DRAIN TO MOP SINK 3. PROVIDE COPPER, INSULATED, CONDENSATE PIPING 4. PROVIDE BACKING AROUND CEILING BOXES 5. DO NOT SUPPORT ANYTHING WITH NYLON BANDS 6. INSTALL FLEX DUCTS AS PER DETAIL ON PLANS |