Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T08CM02922
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/09/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1) WATER DISTRIBUTION AND DWV TEST THRU ROOF OK 2) PIPE WRAPS OK 3) CALL IN 03075 PROGRESS BEFORE SETTING STOOLS AFTER FLOORING IS IN RESTROOM FOR PROPER INSTALLATION OF CLOSET FLANGE INSPECTION |
|
10/07/2008 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PIPING IS COVERED WITHOUT INSPECTION EXPOSE ALL PIPING IN WALL & OVERHEAD FOR INSPECTION COMPLY WITH ALL NOTES FROM 10/2/08 INSPECTION FAILURE TO MAKE CORRECTIONS AND HAVE WORK EXPOSED WILL RESULT IN FUTURE REFEE's |
|
10/02/2008 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE ALL WET MATERIAL FROM DITCH, PROVIDE MINIMUM 1/4" PER FOOT FALL ON ALL 2" & 3" DRAINAGE PIPING AND SHADE WITH DRY MATERIAL 2. PROVIDE LONG RADIUS DISCHARGE FITTINGS FOR HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION 3. PROVIDE MID-SPAN SUPPORTS ON ALL VENT PIPING 4. ALL HORIZONTAL PLASTIC PIPING REQUIRE SUPPORT AT 4' INTERVALS WITH APPROVED HANGERS OR SUPPORTS. 5. PROVIDE FULL SIZE 1" WATER PIPING TO TEE CONNECTION PER PLAN 6. PROVIDE CI PERM CAP AT LAV AREA OF 3 PROVIDE ABS PERM CAPS AT STOOL & LAV AREA OF 3 |