Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM02922
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/09/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/19/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* NEED REVISED AND APPROVED PLANS FOR OUTDOOR LIGHTING - REVISED PLANS TO MATCH RED LINE DRAWINGS IN FIELD |
|
11/18/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLETE ITEMS 7, 8, 9, 10, 11, 15 FROM PREVIOUS INSPECTION 2. ALL STRANDS FOR NEUTRALS & GROUNDS TO BE UNDER TERMINAL LUGS 3. INSTALL MAIN BONDING JUMPER IN SERVICE DISCONNECT 4. GROUNDS & NEUTRAL TO BE SEPARATE IN PANEL 5. DISCONNECT FOR WATER HEATER CANNOT BE HIGHER THAN 6'7" TO HANDLE 6. GEC NOT SIZED PER PLAN AND IS IT GEC GEC TO BE CONTINUOUS |
|
11/17/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED BY CONTRACTOR |
|
11/14/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL BREAKERS LISTED FOR USE IN GE PANEL 2. HAVE PANEL COVER REMOVED FOR INSPECTION 3. NEED DISCONNECTING MEANS FOR WATER HEATER 4. INSTALL EXTENSIONS ON LIGHT SWITCH BOXES IN TILE 5. SEAL OPEN KNOCKOUT @ SERVICE 6. MARK "SERVICE DISCONNECT" 7. NEED TO VERIFY GROUNDING ELECTRODE SYSTEM AND METAL PIPING SYSTEMS ARE BONDED 8. INSTALL PROPER FITTINGS ON SEAL TIGHT 9. GROUNDS #6 & SMALLER TO BE IDENTIFIED ENTIRE LENGTH 10. GROUND EXISTING AC DISCONNECTS AND INSTALL PROPER SIZE GROUND 11. TIGHTEN LOOSE FITTINGS 12. EM LIGHTS TO HAVE CONSTANT FEED 13. PANEL SCHEDULE NOT PER PLAN 14. COUNTER RECEPT PANTRY TO BE GFI |