Permit: T08CM02922

Parcel: 13604328C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM02922

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/09/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/19/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
NEED REVISED AND APPROVED PLANS FOR OUTDOOR LIGHTING - REVISED PLANS TO MATCH RED LINE DRAWINGS
IN FIELD
11/18/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COMPLETE ITEMS 7, 8, 9, 10, 11, 15 FROM PREVIOUS INSPECTION
2. ALL STRANDS FOR NEUTRALS & GROUNDS TO BE UNDER TERMINAL LUGS
3. INSTALL MAIN BONDING JUMPER IN SERVICE DISCONNECT
4. GROUNDS & NEUTRAL TO BE SEPARATE IN PANEL
5. DISCONNECT FOR WATER HEATER CANNOT BE HIGHER THAN 6'7" TO HANDLE
6. GEC NOT SIZED PER PLAN AND IS IT GEC
GEC TO BE CONTINUOUS
11/17/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED BY CONTRACTOR
11/14/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL BREAKERS LISTED FOR USE IN GE PANEL
2. HAVE PANEL COVER REMOVED FOR INSPECTION
3. NEED DISCONNECTING MEANS FOR WATER HEATER
4. INSTALL EXTENSIONS ON LIGHT SWITCH BOXES IN TILE
5. SEAL OPEN KNOCKOUT @ SERVICE
6. MARK "SERVICE DISCONNECT"
7. NEED TO VERIFY GROUNDING ELECTRODE SYSTEM AND METAL PIPING SYSTEMS ARE BONDED
8. INSTALL PROPER FITTINGS ON SEAL TIGHT
9. GROUNDS #6 & SMALLER TO BE IDENTIFIED ENTIRE LENGTH
10. GROUND EXISTING AC DISCONNECTS AND INSTALL PROPER SIZE GROUND
11. TIGHTEN LOOSE FITTINGS
12. EM LIGHTS TO HAVE CONSTANT FEED
13. PANEL SCHEDULE NOT PER PLAN
14. COUNTER RECEPT PANTRY TO BE GFI