Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/19/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/17/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELED BY CONTRACTOR |
|
| 11/10/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. ALL LIGHT FIXTURES TO BE ATTACHED TO GRID 2. ALL LIGHT FIXTURES TO HAVE SEISMIC WIRES 3. CLOSE OPEN JUNCTION BOXES. SEAL OPEN KNOCKOUTS 4. OK CEILINGS IN EXAM ROOMS ONLY NO CEILING TILES TO BE INSTALLED PRIOR TO INSPECTIONS |
|
| 11/07/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/29/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. INSTALL NAIL PLATES AS DISCUSSED THEN OK WALLS 2. OK HARD LIDS |