Inspection Status: Approved
Inspection History: PLUMBING - ROOF DRAINS
Permit Number - T08CM02919
Inspection Description - PLUMBING - ROOF DRAINS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/30/2009 | PLUMBING - ROOF DRAINS | Approved | IVRS - Inspection :* | |
01/29/2009 | PLUMBING - ROOF DRAINS | Denied | IVRS - Inspection : See detailed listing on site.| 999* PIPING COVERED WITHOUT INSPECTION 1. TEST RAIN DRAINS TO OVERFLOW HEIGHT IN TRENCH DRAIN 2. EXPOSE HORIZONTAL PIPING AT (1) LOCATION ON BOTH NORTH & SOUTH SIDES OF DRAINAGE. OVERHEAD PIPING REQUIRES SUPPORT AT 4' INTERVALS AND REQUIRES CORRECT FALL. ADDITIONAL EXPOSURE MAY BE REQUIRED. |
|
01/28/2009 | PLUMBING - ROOF DRAINS | Partial Approval | IVRS - Inspection :* 1. PLUG RELEASED W/WATER DISCHARGE 2. UNABLE TO VERIFY TEST THRU ROOF 3. ALL BUT 1' ACCESS HAS BEEN COVERED 4. PRE-ASSEMBLED PER PLAN REV. NO THIRD PARTY LISTING PROVIDED 5. UNABLE TO VERIFY MATERIAL, JOINTS AND SUPPORT 6. IT APPEARS THAT: a. IT IS NOT PROPERLY SUPPORTED b. SHORT RADIUS FITTINGS WERE USED |
|
01/27/2009 | PLUMBING - ROOF DRAINS | Not ready for Inspection | IVRS - Inspection :* |