Permit: T08CM02919

Parcel: 10714376F


Addresses:

695 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM02919

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/06/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
RECEIVED LETTER PER 514.13
02/05/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. WAITING ON LETTER FOR 514.13
2. AIR PUMP NOT LISTED
3. TIGHTEN ALL FITTINGS AND USE APPROVED FOR LFNMC
02/04/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. USE APPROVED FITTINGS WITH LFNMC AT AIR PUMP
2. WHERE IS DISCONNECTING MEANS FOR AIR PUMP MOTOR
3. PLEASE VERIFY LISTING OF AIR PUMP - NO LABELING PRESENT
4. PROVIDE A LETTER VERIFYING DISCONNECT OF ALL VOLTAGE SOURCES PER 514.13
5. NEED SIGNAGE FOR E STOP 514.11
02/03/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
ALL SEALS NEED TO BE POURED
02/02/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
FINISH POURING ALL SEAL OFF's
OK PACKING
01/30/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
01/29/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. CANNOT STACK LUGS
2. LABEL EQUIPMENT
3. BOND JUMPER TO BE SIZED PER 250.122
4. MAINTAIN WORKING CLEARANCES A/C DISCONNECT - 110.26
5. RECEPTACLE COVER TO BE PER 406.8
6. TIGHTEN CONDUCTOR TERMINATIONS

*OK AT STORE SWITCHGEAR AND CONDUIT IN STORE