Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM02919
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/06/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* RECEIVED LETTER PER 514.13 |
|
02/05/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. WAITING ON LETTER FOR 514.13 2. AIR PUMP NOT LISTED 3. TIGHTEN ALL FITTINGS AND USE APPROVED FOR LFNMC |
|
02/04/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. USE APPROVED FITTINGS WITH LFNMC AT AIR PUMP 2. WHERE IS DISCONNECTING MEANS FOR AIR PUMP MOTOR 3. PLEASE VERIFY LISTING OF AIR PUMP - NO LABELING PRESENT 4. PROVIDE A LETTER VERIFYING DISCONNECT OF ALL VOLTAGE SOURCES PER 514.13 5. NEED SIGNAGE FOR E STOP 514.11 |
|
02/03/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* ALL SEALS NEED TO BE POURED |
|
02/02/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* FINISH POURING ALL SEAL OFF's OK PACKING |
|
01/30/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
01/29/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. CANNOT STACK LUGS 2. LABEL EQUIPMENT 3. BOND JUMPER TO BE SIZED PER 250.122 4. MAINTAIN WORKING CLEARANCES A/C DISCONNECT - 110.26 5. RECEPTACLE COVER TO BE PER 406.8 6. TIGHTEN CONDUCTOR TERMINATIONS *OK AT STORE SWITCHGEAR AND CONDUIT IN STORE |