Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T08CM02919
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/06/2009 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
01/21/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK PVC CONDUITS KIOSK TO AIR STATION AND SIGN *RECEIVED APPROVAL LETTER FROM ENGINEER FOR STATIC GROUNDING |
|
01/15/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK CADWELDS AND GROUND CONNECTION SUBJECT TO ENGINEER APPROVAL |
|
01/14/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK CONDUITS TO TANKS 1. NEED TO SEE CADWELDS FOR GROUNDS 2. BOXES IN CLASSIFIED AREAS TO BE EXPLOSION PROOF |
|
01/12/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK CONDUIT RUNS TO PUMPS OK #4 UFER AT KIOSK |
|
01/09/2009 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
01/07/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* NO MORE THAN 360 DEG. IN CONDUIT RUNS OK TO COVER 20' OUT AROUND KIOSK |
|
01/05/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK PVC CONDUIT KIOSK TO BUILDING |
|
12/19/2008 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* "ASTM" IS A STANDARD NOT A LISTING MARK LISTING MARK MUST BE ON THE PRODUCT NOT PAPER |
|
12/16/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK CONDUITS UNDER KIOSK 1. CORE DRILLED CONDUIT HDPE TO BE AS PER ARTICLE 353 353.6 353.12 353.24 |
|
12/04/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK 7 - 1" IMC CONDUIT STUBS AND 10' FOR CANOPY |