Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/29/2008 | FRAMING | Approved | IVRS - Inspection :* | |
| 10/28/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLY WITH DETAIL 10/DT1 SHEAR TRANSFER OSB TO TOP TOP PLATE, TOE NAIL 12" ON CENTER 2) BLOCK BETWEEN COMBUSTION VENTS GARAGE 3) MISSING BLOCKING SHEARWALL 2 GARAGE 4) PROVIDE WATER TEST DWV, POTABLE WATER OK 5) SHIM BEARING HEADERS 6) DAMAGED FIRE BLOCK MASTER ENTRY 7) PER HOME ENCLOSURE DESIGN NOTES 2, 8 AND 4 UNABLE TO VERIFY ENTRANCE TO BE USED |
|
| 10/27/2008 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED BLK SEPARATING HI-LO COMBUSTION AIR W/HEATER 2. NEED MUD RING FOR UFER 3. NEED TO POUR A SEAL SLAB AT TUB SHOE 4. FURNACE GAS LINE WILL NEED A SEDIMENT TRAP |
|
| 10/20/2008 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER WADE |