Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T08CM02902
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/11/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
01/12/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* BONDING BUSHING OK MARKING LABELING OK |
|
01/09/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. CANNOT USE BONDING LOCKNUT ON CONCENTRIC KNOCKOUTS 2. ALL SERVICES & SERVICE DISCONNECTS TO BE MARKED AND NEED DIRECTORY OR DIRECTION FROM EACH SERVICE TO OTHER SERVICES TO BUILDING 3. OK TO ENERGIZE 150KVA XFMR PANEL DP1, PANEL A & B |
|
11/17/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK HARD LIDS FOR RESTROOMS, PROVIDE DISC. FOR H2O HTR OR BREAKER LOCKOUT |
|
11/12/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK LOBBY WALL #100 |