Permit: T08CM02899

Parcel: 141315810

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T08CM02899

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/18/2008 BUILDING - FINAL Approved IVRS - Inspection :*
12/16/2008 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO PERMIT ON SITE
2) NEED DBL STAMP INSPECTION, STUCCO AND INSULATION CERTS
12/15/2008 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) POST TENSION TAG NEEDED AT HOSE BIBB
2) LABEL NON METALIC PLUMBING AT PANEL
3) RECOMMENDED FUSE SIZE OF 25 AMP FOR WATER HEATER PER MANUFACTURERS SPECS