Permit: T08CM02896

Parcel: 11304001W


Addresses:

1220 E PRINCE RD

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
09/08/2009 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
1) OK TO COVER ALL AREAS
2) TRANSFER "AS BUILT" TO PLAN IN RED INK
08/24/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
07/24/2009 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) PER PLAN APPROVED BY RWS ON 12/19/08: NOT INSTALLED PER PLAN, PLAN CALLS FOR 3" ABS, INSTALLED IS 2" ABS
2) PER PLUMBING NOTE ONE BY RWS ON 12/19/08, PROVIDE A VENT OR AAV FOR EACH FIXTURE, REFERENCE 901.0 2006 UPC, NEW FLOOR DRAIN IN BAR DOES NOT HAVE A VENT
3) REVISE PLAN TO SHOW "AS BUILT" CONDITION, AND PROVIDE A VENT OR AAV FOR FLOOR DRAIN
4) COPPER LOOPED TO BAR IS 1/2" AND IS SOFT SOLDERED. PROVIDE AN APPROVED WATER PLAN ALONG WITH DWV REVISION
5) IF 2" ABS IS APPROVED, SHOW CONNECTION BETWEEN 4" EXISTING CAST IRON, AND NEW 2" ABS
6) PROVIDE TEST ON U.G. ABS
07/23/2009 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*