Permit: T08CM02886

Parcel: 133443810

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08CM02886

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/08/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/30/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PV CONDUCTORS FROM ARRAY TO DISCONNECT RUN THROUGH BUILDING TO BE INSTALLED IN METALLIC RACEWAY
2. FINISH LABELING
3. RECALL WHEN READY
09/26/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEE NOTES LAST INSP.
2. CALLED PER MESSAGE 1:36 PM
09/08/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL BREAKER LISTED FOR USE IN MURRAY PANEL
2. HAVE EQUIPMENT OFF AND OPEN FOR INSPECTION
3. NEED MARKING AND LABELING PER PLANS AND NEC 690
4. PROPERLY STRAP EMT, ANCHORING COMING OUT OF STUCCO
5. CONDUCTORS LARGER THAN #10 INSTALLED IN RACEWAYS TO BE STRANDED
6. ALL GROUNDING ELECTRODES TO BE TIED TOGETHER
7. PROVIDE ACCESS TO ATTIC SPACE