Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/30/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PV CONDUCTORS FROM ARRAY TO DISCONNECT RUN THROUGH BUILDING TO BE INSTALLED IN METALLIC RACEWAY 2. FINISH LABELING 3. RECALL WHEN READY |
|
| 09/26/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEE NOTES LAST INSP. 2. CALLED PER MESSAGE 1:36 PM |
|
| 09/08/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL BREAKER LISTED FOR USE IN MURRAY PANEL 2. HAVE EQUIPMENT OFF AND OPEN FOR INSPECTION 3. NEED MARKING AND LABELING PER PLANS AND NEC 690 4. PROPERLY STRAP EMT, ANCHORING COMING OUT OF STUCCO 5. CONDUCTORS LARGER THAN #10 INSTALLED IN RACEWAYS TO BE STRANDED 6. ALL GROUNDING ELECTRODES TO BE TIED TOGETHER 7. PROVIDE ACCESS TO ATTIC SPACE |