Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T08CM02870

Parcel: 13326327D


Addresses:

165 N SARNOFF DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/17/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) OK FOR FINAL
2) AIR BALANCE OK
08/10/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE FRESH AIR INTAKES AND BALANCE PER PLANS
2) TERMINATE CONDENSATE DRAINS TO AN APPROVED LOCATION
3) SUPPORT PVC ON ROOF EVERY 4'
4) PAINT WITH LATEX PAINT
3) SECURE ELECTRIC DISCONNECTS ON ROOF
4) SUPPORT GAS LINES AND CLAMP