Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/03/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 07/29/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PARTIAL SUPPORT ALL FLEX DUCT EVERY 5' DONOT USE WIRES, WATER PIPES. SUPPORT DIFFUSERS. ALL AIR CONDITIONING DUCTS MUST BE INSULATED WITH A VAPOR BARRIER. PLEASE VERIFY EXISTING A/C UNITS DO NOT EXCEED 2000 CFM. IF THEY DO, ADD DUCT SMOKE DETECTOR. |
|
| 07/27/2009 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO APPROVED MECHANICAL PLANS ON SITE |
|
| 06/04/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* SUSPENDED ROUGH DUCT OK TO PROCEED |