Permit: T08CM02846

Parcel: 141315820

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T08CM02846

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
09/19/2008 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
09/17/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING PLY/OSB SHEAR GARAGE TO HOUSE SHEAR (SEE NEW PLANS)
2) H.D.'S AT SAME WALL TO BE (LTT20B NOT HTT16)
3) INSTALL SIMPSON CS16 STRAPS PER PLAN <8> 1ST & 2ND FLOOR. NEED 11 NAILS TOP BOTTOM ABOVE CLEAN SPAN
4) 11/S1.1 CALLS FOR OSB UP TO ROOF DECK
5) LEAVE TRUSS DRAWINGS PLEASE
6) MISSED #5 INTERIOR SHEAR 1ST FLOOR