Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2008 | FRAMING | Approved | IVRS - Inspection :* | |
| 10/07/2008 | FRAMING | Partial Approval | IVRS - Inspection :* 1) TWO DETAILS, FLR, JOISTS, PERPENDICULAR, PARALLEL SITUATIONS 2) PERPENDICULAR=PLAN DETAIL CALLS FOR 2 X 6 RIBBON AT TRUSS ENDS FOR BRACING, TRUSS WAS MADE FOR 2 X 4. PARALLEL=NO MENTION OF SHEAR TRANSFER AT SPACE BETWEEN FLOORS G-1 DRYWALL SHEAR BELOW 2) ADD STUD 2ND FLOOR SHOWER OVERNOTCHED 3) SUPPORT STAIR LANDING ONLY STUD ONE SIDE CUT 4) SHOWER BACKING VERTICAL 5) CUT NAIL PLATE FRONT BEDROOM MARKED ON FLOOR 6) NEED A FEW HANGERS RAFTER TO LEDGER FRONT ENTRY 7) INQUIRE WITH BLDG OFFICIAL FOR ENGR. PROBLEMS 8) GABLE END DETAIL REQUIRES, FLAT STUD RE-INFORCEMENT FOR STUDS OVER 6'-0" HT |