Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T08CM02845
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/25/2008 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* 1) AT NEXT INSP: OK FROM ENGR. 2 X 6 ON DETAIL 1/SD2 RIBBON/2 X 4 IN FIELD 2) NEED DETAIL SHEAR TRANSFER GARAGE GYP. BOARD TO FLOOR 3) DIAPHRAM IF REQUIRED ? |
|
| 09/23/2008 | EXT METAL CLIPS/EXT SHEATHING | Denied | 1) 2ND FLOOR ELEV. WINDOWS SHEAR NOT PER PLAN 2) G7/G1 SHEAR (SHEETROCK) REQUIRED NEED BELLY BAND REQUIRED DETAIL NOT SHOWING 3) ROOF GIRDERS BRING DBL STUDS DOWN INCLUDING BETWEEN FLOORS 4) INSTALL BLOCKS AT PARALLEL FLOOR JOIST SITUATION 2/SD2 5) A08 ROOF TRUSS REQUIRES T-BRACE 6) 3 PT BEARING FOR DBL GIRDER FRONT, NEED SQUASH BLKS 7) MISSING NAILING ROOF BLOCKING |