Permit: T08CM02842

Parcel: 136371430


Addresses:

3972 S EVERGREEN AV

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
04/03/2009 BUILDING - FINAL Approved IVRS - Inspection :*
10/17/2008 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CARPORT CMU COLUMNS CONSTRUCTED BEFORE INSPECTION UNABLE TO VERIFY PLACEMENT OF REBAR
2. LIGHTS AT FRONT OF CARPORT NEED TO COMPLY WITH LIGHTING ORDINANCE
3. EXTERIOR OUTLETS TO BE GFI PROTECTED
4. 3/AZ COMPLETED PER PLAN (BEAM ATTACHMENT)
5. PERMIT NEEDED FOR ELECTRICAL UPGRADE
6. CONDUIT FOR A/C COMPRESSOR EXCEEDS MAXIMUM BENDS
7. REVISE ELECTRICAL PER AS-BUILT