Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/06/2009 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 12/16/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* SOUTH TRANSFORMER 7 - 3" BUILDING SERVICE 1 - 2 3 - 4" FOR COMMUNICATIONS LETTER APPROVING 3" INSTEAD OF 4" FROM TRANS. TO BUILDING RECEIVED. |
|
| 12/10/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 2 - 4" 7 - 3" AT TRANSFORMER PAD NORTH 4 - 4" FOR COMMUNICATIONS & 2 - 2" THE 7 - 3" STILL NEED TO SEE LETTER FROM ENGINEERING FOR CHANGE FROM 4" TO 3" |
|
| 11/13/2008 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK 2' FOR HOUSE PANEL TO TRANS OK 4 - 1' FOR JUNCTION BOX FOR OUTSIDE LIGHTING |