Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T08CM02825
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/15/2010 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
03/15/2010 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) NEED ILLUMINATION AT HOUSE PANEL 2) NEED LETTER OF TORQUE FOR SWITCH GEAR 3) SERVICE ENTRANCE NOT PER EXCEPTION #1 230.40 OR 230.71 4) SERVICE NOT LISTED AS SUITABLE AS SERVICE EQUIPMENT |
|
03/08/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK CADWELDS AND METAL PIPING BONDS 2) OK ENTRY CEILINGS 1ST & 2NS FLOOR EXTERIOR 3) OK CONDUITS IN CHASE |
|
02/19/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |