Permit: T08CM02806

Parcel: 12007228F


Addresses:

333 W AJO WY


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T08CM02806

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
01/07/2010 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
12/29/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEMS 7 AND 8 DATED 10/13/09 NOT COMPLETE AT THIS TIME
2) ITEM 13 DATED 10/13/09 NOT COMPLETE
3) ALL PVC EXPOSED TO EXTERIOR TO BE PAINTED
10/13/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REMOVE TAPE FROM EXPOSED DUCT, SEAL PER PLANS
2) PROVIDE HANGERS ON EXPOSED DUCT PER PLANS
3) SEAL ALL DUCT JOINTS
4) VERIFY UNIT A C-B DUCT ABOVE CEILING IS INSULATED
5) REMOVE ALL TAPE FROM FLUE PIPE, PROVIDE MIN. 3 SCREWS
6) FLUE PIPING NOT TO EXCEED 60 DEGREE HORIZONTAL
7) PROVIDE PROPER SIZE FILTERS
8) PROVIDE FILTERS ON NEW UNIT OUTSIDE AIR
9) PROVIDE EXISTING UNIT WITH OUTSIDE AIR
10) CONDENSATE TO TERMINATE AT AN APPROVED LOCATION
11) PROVIDE AIR BALANCE REPORT PER SPECS
12) DISCONNECT BOXES DO NOT OPEN, UNABLE TO CHECK FUSES
13) ALL PVC PIPE JOINTS TO BE PRIMED PRIOR TO GLUE, PRIMER TO BE PURPLE IN COLOR
07/27/2009 MECHANICAL - ABOVE CEILING Partial Approval 1) ALL ITEMS DATED 7/17/09 HAVE BEEN CORRECTED
2) THERE ARE TWO VISIBLE DUCT DROPS (EXISTING) WHICH HAVE APPROX. 20" DIAGONAL HOLES BLOWING AIR INTO ABOVE CEILING SPACE, THESE ARE FROM THE EXISTING SYSTEMS THAT ARE TO REMAIN, THEY NEED TO BE PATCHED SEALED AND INSULATED, COMPLETE PRIOR TO NEXT INSPECTION
07/24/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FLEX NOT INSTALLED PER PLANS
2) A REFEE IS ASSESSED TO THIS ACTIVITY
07/23/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
07/17/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL FLEX PER DETAIL M-3 (110)
2) PROVIDE TAPE PER DETAIL M-3 (110)
3) PROVIDE FULL RADIUS BENDS IN FLEX
4) ALL SUPPLY/RETURN DUCT TO BE INSULATED
5) ALL DUCT JOINTS INCLUDING EXHAUST TO BE SEALED
6) PROVIDE MECHANICAL FASTENERS AT ALL EXHAUST JOINTS
7) ALL DIFFUSER BOXES TO BE FRAMED MINIMUM 3 SIDES
11/13/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
AC-1 DUCT ABOVE CEILING OK
OK TO SHEETROCK THIS AREA
10/30/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO SHEETROCK WEST SIDE OF OFFICE
10/24/2008 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
THIS PROJECT IS BEING DONE IN PHASES
AC-2 IS THE ONLY WORK BEING DONE AT THIS TIME

1. INSTALL DUCT PER PLANS
2. SEAL RETURN AIR DUCT