Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T08CM02806
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/07/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
12/29/2009 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEMS 7 AND 8 DATED 10/13/09 NOT COMPLETE AT THIS TIME 2) ITEM 13 DATED 10/13/09 NOT COMPLETE 3) ALL PVC EXPOSED TO EXTERIOR TO BE PAINTED |
|
10/13/2009 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE TAPE FROM EXPOSED DUCT, SEAL PER PLANS 2) PROVIDE HANGERS ON EXPOSED DUCT PER PLANS 3) SEAL ALL DUCT JOINTS 4) VERIFY UNIT A C-B DUCT ABOVE CEILING IS INSULATED 5) REMOVE ALL TAPE FROM FLUE PIPE, PROVIDE MIN. 3 SCREWS 6) FLUE PIPING NOT TO EXCEED 60 DEGREE HORIZONTAL 7) PROVIDE PROPER SIZE FILTERS 8) PROVIDE FILTERS ON NEW UNIT OUTSIDE AIR 9) PROVIDE EXISTING UNIT WITH OUTSIDE AIR 10) CONDENSATE TO TERMINATE AT AN APPROVED LOCATION 11) PROVIDE AIR BALANCE REPORT PER SPECS 12) DISCONNECT BOXES DO NOT OPEN, UNABLE TO CHECK FUSES 13) ALL PVC PIPE JOINTS TO BE PRIMED PRIOR TO GLUE, PRIMER TO BE PURPLE IN COLOR |
|
07/27/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | 1) ALL ITEMS DATED 7/17/09 HAVE BEEN CORRECTED 2) THERE ARE TWO VISIBLE DUCT DROPS (EXISTING) WHICH HAVE APPROX. 20" DIAGONAL HOLES BLOWING AIR INTO ABOVE CEILING SPACE, THESE ARE FROM THE EXISTING SYSTEMS THAT ARE TO REMAIN, THEY NEED TO BE PATCHED SEALED AND INSULATED, COMPLETE PRIOR TO NEXT INSPECTION |
|
07/24/2009 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FLEX NOT INSTALLED PER PLANS 2) A REFEE IS ASSESSED TO THIS ACTIVITY |
|
07/23/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
07/17/2009 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL FLEX PER DETAIL M-3 (110) 2) PROVIDE TAPE PER DETAIL M-3 (110) 3) PROVIDE FULL RADIUS BENDS IN FLEX 4) ALL SUPPLY/RETURN DUCT TO BE INSULATED 5) ALL DUCT JOINTS INCLUDING EXHAUST TO BE SEALED 6) PROVIDE MECHANICAL FASTENERS AT ALL EXHAUST JOINTS 7) ALL DIFFUSER BOXES TO BE FRAMED MINIMUM 3 SIDES |
|
11/13/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* AC-1 DUCT ABOVE CEILING OK OK TO SHEETROCK THIS AREA |
|
10/30/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO SHEETROCK WEST SIDE OF OFFICE |
|
10/24/2008 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* THIS PROJECT IS BEING DONE IN PHASES AC-2 IS THE ONLY WORK BEING DONE AT THIS TIME 1. INSTALL DUCT PER PLANS 2. SEAL RETURN AIR DUCT |