Permit: T08CM02806

Parcel: 12007228F


Addresses:

333 W AJO WY


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T08CM02806

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
01/07/2010 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
12/03/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
OUTSIDE BUILDING TIE IN OK (ONLY)
11/20/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) 4" INSTALLED FROM 2 WAY CLEANOUT AND AT BLDG TO TIE IN ONLY
2) PROVIDE TEST AND TRACER WIRE
10/09/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) COMPLETE PLUMBING PLAN NOTE #24
2) INSTALL THERMOSTATIC MIXING VALVE PER PLAN
3) HAVE APPROVED RED LINES ON SITE
4) LETTER FOR TYPE M COPPER
06/10/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. TEST ON ROUGH SOIL OK
2. PROVIDE APPROVED PLAN FROM CITY FOR ALL CHANGES
3. CALL BACK FOR PRE-SLAB
06/09/2009 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. UNCOVER ALL FITTING
2. PROVIDE FULL SIZE 3" CLEANOUT PER APPROVED PLANS
3. STOP WATER FROM DRIPPING
06/05/2009 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL PER APPROVED PLAN FOR BUILDING DRAIN (4")
2. PROVIDE FULL SIZE UPPER TERMINAL CLEANOUT
3. NOTE: P-4 FIXTURE TYPICALLY REQUIRES
UNDERGROUND P-TRAP
4. PROVIDE MINIMUM FALL ON ALL DRAINAGE PIPING