Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2009 | MECHANICAL - FINAL | Approved | ||
| 10/08/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) EXTEND WATER HEATER VENT MINIMUM 2' ABOVE PARAPET WALL 2) PROVIDE A DISCONNECT FOR MAKE UP AIR UNIT 3) INSTALL ELECTRIC TO EXHAUST FAN PER MANUFACTURERS SPECS 4) PROVIDE GREASE RECEPTOR ON EXHAUST FAN 5) OK FOR ANSUL TEST 6) AIR BALANCE OK 7) CAPTURE AND CONTAINMENT OK |