Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2009 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
| 08/05/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) FIRE WRAP OK 2) OK TO SHEETROCK HARD LIDS 3) OK TO INSTALL 12" X 12" ACCESS DOOR IN GREASE DUCT 4) SEAL ALL DUCT WORK PER PLANS 5) PROVIDE A LETTER FROM ENGINEER IF NOT FOLLOWING DETAILS 6) USE ONLY UL 181 TAPE AND MASTIC |
|
| 07/31/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) CHECKED 1ST LAYER OF FIRE WRAP, OK FOR 2ND LAYER |
|
| 07/30/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* CHECKED WELDS ON GREASE DUCTS - OK TO FIRE WRAP 2 LAYERS UPPER SECTION ONLY. OK TO INSTALL GREASE DUCTS AND HOOD. CHECKED CONDENSATE DRAIN. OK TO INSULATE AS PER PLANS |
|
| 07/27/2009 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* 1) COURTESY INSPECTION DISCUSSED HOOD CLEARANCES |