Permit: T08CM02792

Parcel: 133095070


Addresses:

7865 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T08CM02792

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/28/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) WILL CHECK CORRECTIONS ON FINAL
2) LETTERS FROM ENGINEER OK
3) OK FOR CEILING TILES
09/17/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SUPPORT DIFFUSERS TO STRUCTURE
2) PROVIDE INSTALL INSTRUCTIONS FOR CLEANOUT ON GREASE DUCT
3) PROVIDE LETTER FROM ENGINEER ALLOWING FLEX DUCT OVER 5'
4) MAKE UP AIR NOT INSTALLED PER PLAN
5) EXHAUST FAN MUST TERMINATE AT TOP OF PARAPET
6) PROVIDE HINGE KIT
7) NOTE: DO NOT SUPPORT SODA LINES FROM CONDUITS OR WITH ZIP TIES
09/08/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) ITEMS 4,3 AND 5 DATED 8/5/09 STILL NOT COMPLETE
2) FLEX DUCT NOT TO EXCEED 5' PER SPECS
3) PROVIDE N.E. TAPS PER PLANS
4) PROVIDE SEISMIC WIRES ON ALL T-BAR REGISTERS
5) INSULATE ALL CONDENSATE PIPING