Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T08CM02792
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/28/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1) WILL CHECK CORRECTIONS ON FINAL 2) LETTERS FROM ENGINEER OK 3) OK FOR CEILING TILES |
|
09/17/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUPPORT DIFFUSERS TO STRUCTURE 2) PROVIDE INSTALL INSTRUCTIONS FOR CLEANOUT ON GREASE DUCT 3) PROVIDE LETTER FROM ENGINEER ALLOWING FLEX DUCT OVER 5' 4) MAKE UP AIR NOT INSTALLED PER PLAN 5) EXHAUST FAN MUST TERMINATE AT TOP OF PARAPET 6) PROVIDE HINGE KIT 7) NOTE: DO NOT SUPPORT SODA LINES FROM CONDUITS OR WITH ZIP TIES |
|
09/08/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) ITEMS 4,3 AND 5 DATED 8/5/09 STILL NOT COMPLETE 2) FLEX DUCT NOT TO EXCEED 5' PER SPECS 3) PROVIDE N.E. TAPS PER PLANS 4) PROVIDE SEISMIC WIRES ON ALL T-BAR REGISTERS 5) INSULATE ALL CONDENSATE PIPING |