Permit: T08CM02778

Parcel: 141176860

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T08CM02778

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/03/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
04/01/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
- PROVIDE CHLORINE & BACTERIA REPORT FOR POTABLE WATER SUPPLY.
- PROVIDE IN HOUSE BACKFLOW CERTIFICATIONS.

1. EXPOSE ALL CLEANOUTS
2. PROVIDE TEMPERING TO NOT EXCEED 110 DEG. AT PUBLIC USE LAVS HOT WATER SUPPLY
3. CONDENSATE TO TERMINATE AT VERTICAL BRANCH TAILPIECE UPSTREAM OF P-TRAP
4. PROVIDE LISTING, 1" AIR GAP OR BACKFLOW PROTECTION FOR ICE MACHINE WATER SUPPLY
5. LABEL PROCESS LIQUID PIPING AND POTABLE WATER PIPING IN PROCESS PIPING ROOM
6. BREAK OFF TAMPER SCREW ON VACUUM BREAKER FOR HOSE BIB
7. REMOVE RESTRICTION IN CONDENSATE DRAINS AT LAVS