Permit: T08CM02775

Parcel: 127022650


Addresses:

5320 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/30/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
ALL CORRECTIONS HAVE BEEN MADE
08/18/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE FRESH AIR INTAKES ON AC UNITS
2. MARK UNIT DATA PLATES W/PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY
3. PROVIDE A GFI SERVICE RECEPTACLE WITHIN 25' OF EQUIPMENT
4. CONDENSATE CANNOT TERMINATE ONTO THE ROOF
5. TERMINATE TO AN APPROVED LOCATION