Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08CM02770
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/28/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RECEPTS IN INDUSTRAIL COVERS TO BE SECURED/SUPPORTED BY MINIMUM 2 SCREWS 2) COULD NOT LOCATE CIRCUIT FOR LIGHTS IN OFFICE. CIRCUIT #9 DOES NOT FEED THIS AREA 3) SEAL OPEN KNOCKOUTS IN LIGHT FIXTURES IN WAREHOUSE. FIXTURES APPEAR NOT TO BE CHAIN HUNG PROPERLY 4) PLEASE PROVIDE INSTRUCTIONS |