Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/06/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/04/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK 2ND FLOOR FOR ELECTRIC FINAL #33 1. GFI NEEDED AT SINK 2. BOX TO FAR IN CORNER 3. PANEL MORE THAN 1/4" FROM SURFACE 4. CLEAN BREAKERS *FINISH #34 AND 8 PREVIOUS INSPECTION |
|
| 04/27/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SECURE NM CABLE TO BOX 2. GROUND METAL BOXES 3. FULLY COVER BOXES WITH DEVICE AND PLATES 4. CANNOT MIX STRANDED AND SOLID CONDUCTOR IN GROUND BARS 5. FILL UNUSED OPENINGS IN BOXES AND PANEL 6. BREAKER STILL NOT LABELED 7. FINISH CLEANING UNDER GROUND BARS 8. FINISH LABELING PANELS AS PER 408.4 |
|
| 04/01/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* OK ROUGH ELECTRIC 30-32 1-8: 1. FINISH OUTLETS 2. GROUND BARS - CLEAN SURFACE AND NO SHEETMETAL THREAD SCREWS 3. FINISH EXTENDING OUTSIDE WALL LIGHT RINGS |
|
| 03/27/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
| 03/19/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
| 03/12/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK 16-24 AND 25-30 1. FILL UNUSED OPENINGS PANELS AND BOXES 2. LABEL BREAKERS |
|
| 03/11/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/03/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. ONLY ONE CONDUCTOR PER SCREW TERMINAL AT LIGHTS 2. TIGHTEN GROUND TERMINATIONS AT SWITCHES 3. BOXES MORE THAN 1/4" 4. USE APPROVED HARDWARE FOR DEVICES |
|
| 02/20/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NOTE: NEUTRAL NOT TO BE SHARED ON MULTI-CIRCUITS ON SAME BREAKER |
|
| 02/19/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 9-10-11: 1. DRYWALL SCREWS NOT ALLOWED FOR GROUNDING 2. SUPPORT CABLES ABOVE PANEL 3. GROUND BAR HAS TOO MANY CONDUCTORS 4. STAPLE NM CABLE OK WALLS EXCEPT AT PANEL 30: 1. LABEL PANEL DIRECTORY 408.4 |