Permit: T08CM02756

Parcel: 125111880


Addresses:

770 N DODGE BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/06/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/04/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK 2ND FLOOR FOR ELECTRIC FINAL

#33
1. GFI NEEDED AT SINK
2. BOX TO FAR IN CORNER
3. PANEL MORE THAN 1/4" FROM SURFACE
4. CLEAN BREAKERS

*FINISH #34 AND 8 PREVIOUS INSPECTION
04/27/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. SECURE NM CABLE TO BOX
2. GROUND METAL BOXES
3. FULLY COVER BOXES WITH DEVICE AND PLATES
4. CANNOT MIX STRANDED AND SOLID CONDUCTOR IN GROUND BARS
5. FILL UNUSED OPENINGS IN BOXES AND PANEL
6. BREAKER STILL NOT LABELED
7. FINISH CLEANING UNDER GROUND BARS
8. FINISH LABELING PANELS AS PER 408.4
04/01/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
OK ROUGH ELECTRIC 30-32

1-8:
1. FINISH OUTLETS
2. GROUND BARS - CLEAN SURFACE AND NO SHEETMETAL THREAD SCREWS
3. FINISH EXTENDING OUTSIDE WALL LIGHT RINGS
03/27/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
03/19/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
03/12/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK 16-24 AND 25-30
1. FILL UNUSED OPENINGS PANELS AND BOXES
2. LABEL BREAKERS
03/11/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/03/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. ONLY ONE CONDUCTOR PER SCREW TERMINAL AT LIGHTS
2. TIGHTEN GROUND TERMINATIONS AT SWITCHES
3. BOXES MORE THAN 1/4"
4. USE APPROVED HARDWARE FOR DEVICES
02/20/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NOTE: NEUTRAL NOT TO BE SHARED ON MULTI-CIRCUITS ON SAME BREAKER
02/19/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
9-10-11:
1. DRYWALL SCREWS NOT ALLOWED FOR GROUNDING
2. SUPPORT CABLES ABOVE PANEL
3. GROUND BAR HAS TOO MANY CONDUCTORS
4. STAPLE NM CABLE

OK WALLS EXCEPT AT PANEL

30:
1. LABEL PANEL DIRECTORY 408.4