Permit: T08CM02730

Parcel: 11012007B


Addresses:

5151 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T08CM02730

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/16/2009 ELECTRIC - INTERMEDIATE Approved
01/26/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
STORAGE ROOM JR. BALLROOM WALL OK
MC NEEDS STRAPPING 12" FROM BOXES IN CEILING AND LOW VOLTAGE NEED STRAPPING
01/12/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/07/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/18/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK HARD LIDS RESTROOMS OUTSIDE RANCHERS CLUB
INSTALL ACCESS PANEL TO SERVICE AIR HANDLER
2. OK SOFFITS OUTSIDE RANCHERS CLUB
12/03/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS EXERCISE ROOM
11/24/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. INSTALL NAIL PLATES AS DISCUSSED THEN OK WALLS & SOFFIT AT CAFE

RECEIVED CHECK FOR $300 CHK#108348
FOR EXTRA INSPECTIONS PER LEERAY
11/17/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ALL FIXTURES TO HAVE SEISMIC WIRES
2. HAVE OPEN WIRING AND SIGNS
3. REMOVE CORDS AND LIGHTS FROM ABOVE CEILING
4. PROPERLY SUPPORT LOW VOLTAGE WIRING
5. MISSING EM LIGHTS PER PLAN
6. INSTALL ACCESS DOORS AS PREVIOUSLY DISCUSSED
7. SEAL OPEN KNOCKOUT JUNCTION BOXES
8. SUPPORT MC CABLE EVERY 6'
9. ANY OLD WIRING TO BE REMOVED
10. BUILDING INSPECTOR NEEDS TO DO ABOVE CEILING INSPECTION
11/14/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED ACCESS PANELS FOR JUNCTION BOXES ABOVE HARD LIDS IN RESTROOMS BASEMENT
2. NEED TO REMOVE CEILING TILES IN BASEMENT FOR INSPECTIONS
10/15/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK ROUGH ELECTRIC @ BAR AREA
2. OK HARD LIDS AND WALLS CAFE EXCEPT STARBUCKS COUNTER WALL. INSTALL NAIL PLATES ON FURRING STRIPS AS DISCUSSED.